Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

News

News

209 articles filed under News.

High room humidity: five checks, in order

Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.

InsightRead

When a signal cable screen is earthed at both ends

A room pressure signal that wanders when a drive ramps often has a cable screen bonded at both ends, carrying earth current beside a 4–20 mA signal. For analogue signals, bond the screen at one end, keep it continuous and insulated through junction boxes, and follow the instrument maker where the instruction differs.

InsightRead

The accelerated stability condition: 6 months at 40 °C / 75% RH

The ICH stability guideline sets the accelerated study at 40 °C ± 2 °C and 75% RH ± 5% RH for a minimum of 6 months. If long-term studies run at 25 °C/60% RH, a significant change there should be followed by intermediate testing. For the chamber, excursions beyond the tolerances for more than 24 hours should be described in the study report.

InsightRead

Open ductwork on site and short-lived terminal HEPAs

Construction dust left in supply ducts ends up in the terminal HEPA filters, which then load in months. Order ductwork factory-cleaned and capped, store it off the floor, re-cap every open end at the end of each shift, inspect and wipe each section before connection, and fit the terminal filters last.

InsightRead

What an f2 of 50 says about two dissolution profiles

The similarity factor f2 compares two dissolution profiles on a scale where 100 is identical and a 10% difference at every time point gives 49.9. FDA and EMA guidance read 50 to 100 as similar, under conditions on units, time points and variability. It is one input to a comparison after a site change.

InsightRead

An ISO 8573-1:2010 class such as [1:2:1] is three limits in a fixed order: particles, water as pressure dew point, and total oil. Class 2 water is −40 °C or lower; class 1 oil is 0.01 mg/m³ or less. The class does not name a location, so state the point of use.

InsightRead

Before reusing last project's detail

A cooling coil detail reused from a previous project brings that project's entering air condition with it. In a 100% outdoor air unit the same rows can meet sensible capacity and leave the supply air too wet. Find the design basis, mark what differs, recalculate, and write the source on the calculation.

InsightRead

What a capacitor bank saves, and what it does not

A capacitor bank supplies reactive current next to the load. The load's kW is unchanged, and kWh fall by no more than the cable and transformer loss saved upstream of the bank, under 1% in a worked example. The payback is the reactive charge billed in Viet Nam below a power factor of 0.9 and the transformer capacity freed.

InsightRead

An alarm that appears on a screen in an empty control room has not been delivered. Test the notification chain: every route delivers, the time from event to receipt is measured, escalation works when nobody acknowledges, the out-of-hours list is current, and a failed message service raises its own alarm.

InsightRead

A variable-speed chilled-water pump that holds design head across its own headers hardly slows down. In a 300 kPa example, a sensor at the index coil brings the head down to 120 kPa at half flow. The US energy standard ASHRAE 90.1 requires measurement at or near the most remote heat exchanger and, with DDC, setpoint reset from valve positions.

InsightRead