Reading ISO 29463 HEPA labels against EN 1822

ISO 29463 labels encode efficiency: ISO 35H is at least 99.95% and ISO 45H at least 99.995%, the integral efficiencies of EN 1822 H13 and H14. ISO 40H sits between them with no EN 1822 name and passes twice as many particles at MPPS as 45H. Name the accepted equivalent in the specification.

InsightRead

Water needs about 2,450 kJ/kg to evaporate, so every kg/h leaving a mopped floor or wash bay adds about 0.68 kW of latent load. It arrives after production, when the cooling coil unloads. Treat the cleaning shift as its own dehumidification design case.