WHO's 2022 GMP for sterile products (TRS 1044, Annex 2) follows EU Annex 1. For a WHO-prequalification plant the barrier comes first: a RABS needs a Grade B background, a closed isolator Grade D, and that sets the HVAC. The contamination control strategy should be written alongside the design.
A spring isolator with its transport bolt still fitted transmits everything. Remove transport locks, select isolators for the lowest drive speed, keep flexible connections slack, remove rigid bridges such as conduit or drain lines, use inertia bases where needed, and file the balance report and a vibration baseline.
21 CFR 11.10(e) requires secure, computer-generated, time-stamped audit trails. For an environmental monitoring system, that means the software logs setpoint, alarm-limit and user changes itself, nobody can purge entries, every clock follows one time source, and the requirements sit in the URS before a platform is chosen.
Annex 1 leaves Grade B particle monitoring frequency and sample size to the site. A sequential counter with 8 one-minute ports revisits each point about every 8 minutes, so a 3-minute event can be missed. Set locations from the smoke study, frequency from the events, and justify both in the CCS.
Each kilogram of electrolytic hydrogen needs at least 9 kg of water, and at 75% RO recovery that means 12 kg of feed. Pharma water habits such as sampling plans, trended conductivity and buffer storage transfer well. A WFI-style loop may not: build to the electrolyser supplier's feedwater specification.
A classified room's air change rate, recovery time and pressure steps were proved at one airflow. Constant volume holds each room's flow at that value with a terminal, while the fan speeds up as filters load. VAV moves supply with the cooling load, so it belongs in offices, technical areas and fume-hood exhaust.
The PIC/S GMP Guide and EU GMP are almost identical, revised Annex 1 included. In the EU the GMP principles are set in law and certificates sit in EudraGMDP; PIC/S authorities adopt the guide nationally and PIC/S certifies nothing. One design serves both; the EU inspection route is planned separately.
A 15–25 °C store in Viet Nam needs active cooling. Split units give cheap N+1 redundancy but a short air throw and little humidity control. A chilled-water AHU ducts air to the top of tall racking and can control dew point, with dearer redundancy. Humidity limits on the labels usually decide it.
When deviations, change control and EM trends live in different systems, one event can carry three dates. Rehearse the first-hour inspection requests by pulling all seven records for one day six months back, then check that each system gives the same date and cross-reference for it.
An AHU casing is described by five EN 1886 classes: strength D1–D3, leakage L1–L3, filter bypass up to F9, thermal transmittance T1–T5 and thermal bridging TB1–TB5. A witnessed FAT can test leakage on the real unit; transmittance and bridging come from a laboratory model box, so the model box report belongs with the offer.
A depyrogenation tunnel runs from the wash room into a Grade B filling room, across one or two grade steps, and releases heat next to the Grade A zone. Its own airflow balance and heat release per zone belong in the design basis, and the rooms are balanced with the tunnel at temperature.
Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated. A yearly meeting catches changes late. Adding one question to every HVAC change control, EM adverse trend review and deviation closure form, asking whether the CCS still says the right thing, keeps it current with the site.