Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

News

News

209 articles filed under News.

Charged media: new efficiency vs discharged efficiency

Electrostatically charged filter media lose efficiency as the charge drains in service, while pressure drop barely changes. EN 779:2012 added a discharged minimum for F7 to F9; ISO 16890 rates ePM as the average of initial and discharged efficiency. Buy pre-filters on that rating.

InsightRead

Duct airtightness classes: each step is 3× tighter

Duct airtightness classes A to D each allow about a third of the leakage of the class before. At 400 Pa, 500 m² of class B ductwork may leak about 220 l/s, class C about 75 l/s. Leakage after the flow control point moves the pressure cascade without the controller noticing.

InsightRead

Hold cleanroom pressure on the extract side

A cleanroom is qualified on its supply airflow: air change rate, recovery time and hood velocity. Controlling room pressure by trimming supply moves those numbers with every door opening. Holding supply constant and modulating extract or return keeps the qualified airflow and still holds the pressure cascade.

InsightRead

16 sampling locations where there used to be 10

ISO 14644-1:2015 replaced the square-root rule for classification sampling locations with Table A.1. A 100 m² room went from 10 locations to 16. The revision also dropped the 95% UCL calculation and asks for one location per section of equal area. Requalification plans written before 2016 should be checked against the table.

InsightRead

What the EMS never saw: logging interval vs deadband

A 20-second excursion can fall between two 1-minute log entries, and a change-of-value deadband can store a slow drift as a flat line. Set the logging interval shorter than the shortest event that matters and the deadband smaller than the smallest drift, and evaluate alarms in the controller.

InsightRead

The water your AHU sends to the drain

Drying 10,000 m³/h of wet-season air from a 26 °C to a 9 °C dew point removes about 170 kg of water an hour, roughly 4 m³ a day at full load. The condensate is low in minerals and a candidate for reuse such as cooling tower make-up, after a site assessment.

InsightRead

Why a 0.98 board can read 0.91

True power factor is displacement power factor multiplied by a distortion factor. At 40% THDi that factor alone caps true PF near 0.93, so a board corrected to 0.98 DPF still reads about 0.91. More capacitors cannot close that gap; DC chokes and harmonic filters sized from a study can.

InsightRead

A desiccant dehumidifier selection depends on six inputs: fresh and return airflow, air condition after pre-cooling, target dew point, reactivation heat source, leakage allowance and redundancy. −40 °C dew point is about 0.08 g/kg and −60 °C under 0.01 g/kg, a step that can add a rotor stage.

InsightRead

Work it by hand before you trust the program

A selection program will size a coil for any input, including a wrong one. Engineers who have worked the psychrometric chart by hand notice when an answer is off. Humiley's training pairs fundamentals with on-the-job work on real project packages, mentored by senior leads, starting from a 12-month internship.

InsightRead

For the same excess airflow, room pressure differential varies with the inverse square of the leakage area. On a finished cleanroom that area hides in door gaps, ungasketed light fittings, open socket boxes, panel joints and penetrations. Compare measured excess air with the design allowance at commissioning.

InsightRead

Shrink an AHU cross-section by 10% and the air moves about 11% faster, while pressure drop across the coil and dampers rises about 23%. At 10,000 m³/h that is roughly 0.4 kW, about 3,800 kWh a year. Ask bidders for coil face velocity and the EN 13053 velocity class.

InsightRead