EN 1822 classes the filter, not the medium. PTFE membrane usually reaches a HEPA class at lower pressure drop and handles better than brittle glass fibre, but its surface catches oil aerosol from leak tests. Agree the test aerosol with the filter maker before specifying PTFE for pharma rooms.
In a potent-compound suite the exhaust HEPA collects the compound for its whole life. A bag-in/bag-out housing needs gas-tight isolation dampers, a bag change in which the ring never opens to the room, ports for in-place leak testing and space to work the bag, plus a written procedure and trained technicians.
EN 1886 classes AHU casing strength by deflection at test pressure: D1 up to 4 mm/m, D2 up to 10 mm/m. On a high-static GMP supply unit, a flexing panel works its gaskets loose and leakage rises. Ask which class was tested, on what model box, and whether your design pressure fits.
A walk-on cleanroom ceiling turns the void into a service floor, so dampers, sensors, cables and lighting are maintained without entering the room. It only helps filter changes if the HEPA housings are top-serviceable, and the void must be designed as a floor. Worth it for plant-heavy suites, rarely for small labs.
Infectious isolation rooms are held negative to protect the corridor; protective isolation rooms are held positive to protect the patient. The anteroom works the same way for both. A switchable room needs its failure mode designed: mode and pressure display at the door, local alarm, signed switching and dampers that fail safe.
Annex 1 initial validation of an aseptic process needs at least 3 consecutive successful simulations covering all working shifts, then periodic runs twice a year per process, line and shift. The cleanroom must hold its qualified state throughout. Agree an HVAC freeze date with QA, and list in advance which jobs are like-for-like and which need an impact assessment.
Put containment exhaust fans at the end of the run so ducts inside the building stay negative. Run duty and standby with isolation dampers and alarmed changeover, discharge vertically with height and velocity from a standard or a dispersion study, and keep the plume away from fresh-air intakes.
A shared exhaust duct spreads a solvent's hazardous zone, cakes process dust in humid air, carries potent-compound contamination through the building if joined upstream of the HEPA, and moves fume-hood face velocity with other dampers. Draw each stream with its hazard, treatment and fan first.
A pre-filter changed at 150 Pa on a 0–1,000 Pa gauge sits in the bottom 15% of the dial with about 20 Pa of uncertainty. A 0–250 Pa gauge puts it at 60% with 5 Pa. Range each stage's gauge and transmitter to its own change point.
A depyrogenation tunnel runs from the wash room into a Grade B filling room, across one or two grade steps, and releases heat next to the Grade A zone. Its own airflow balance and heat release per zone belong in the design basis, and the rooms are balanced with the tunnel at temperature.
A V-belt sheds rubber dust into the airstream for its whole life, and in a GMP supply AHU that dust loads the final filters. Belt drives also lose a few per cent of shaft power and need regular tensioning. Direct-drive plug fans avoid all three, though a large belt-driven housed fan can still win at high pressure.
EN 1822 rates HEPA filters at the most penetrating particle size, typically 0.1–0.25 µm for glass-fibre media, while US practice quotes 99.97% at a fixed 0.3 µm. Because 0.3 µm is above the MPPS, the two numbers come from different tests and cannot be compared line by line on a datasheet.