Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Life Sciences

Life Sciences

379 articles filed under Life Sciences.

Dust collectors in OSD plants: media, explosion protection and location

Lactose, starch and microcrystalline cellulose are combustible dusts, and the granulation dust collector is one of the places that concentrates them. Test the blend for explosibility first, protect with venting, flameless venting or suppression plus inlet isolation, site the collector where a vent can discharge safely, then choose cartridge or bag media.

InsightRead

Calibration before OQ: installed transmitters count too

An OQ report can list certificates for every test instrument and none for the room pressure transmitters it reads. Before the first test, one sheet should cover both groups: certificate number, due date against the last test day and calibrated range against the test value, for the test kit and the installed sensors alike.

InsightRead

Energy recovery in once-through potent suites

Many potent suites recirculate through safe-change HEPA housings; where the risk assessment rules that out, every cubic metre is tropical outdoor air. Run-around coils recover heat with the airstreams fully separated, wheels open a leakage path, and dedicated fresh-air pre-cooling targets the latent load. Our energy modeling targets a 30% HVAC energy reduction.

InsightRead

WFI without a still: what changed in 2017

Since April 2017, Ph. Eur. monograph 0169 permits WFI by non-distillation methods such as RO with further purification, with the same endotoxin limit of 0.25 IU/mL. The loop can still run hot; what changes is a generator at ambient, whose sanitization, integrity checks and online monitoring must be settled before the P&ID.

InsightRead

Mixing air lowers the average particle count but cannot sweep a particle off an open vial. Unidirectional airflow is checked by air speed, with an Annex 1 guidance range of 0.36–0.54 m/s, and a filmed smoke study; a mixed-flow room by its 100:1 recovery time (ISO 14644-3).

InsightRead

When the SCADA admin also runs the shift

PIC/S PI 041-1 expects system administrator rights to sit apart from people who generate or approve GMP data, where possible. On small sites one engineer often does both. The conflict can be controlled: named separate accounts, admin activity reviewed by QA or IT, and configuration changes through change control.