"Quality is QA's job" is not how the GMP texts read. The 2013 text of EU GMP Chapter 1 makes the quality objective the responsibility of senior management, with staff in many departments taking part. Chapter 2 lists qualification and maintenance of premises and equipment among the duties the heads of Production and Quality Control generally have.
The ASEAN Common Technical Dossier, ACTD, organizes a registration dossier in four parts: administrative data and product information, quality, nonclinical and clinical. The ICH CTD has five modules because it collects all summaries in Module 2. The quality science is the same; the arrangement and numbering differ.
Operators run the plant from BMS graphics, so errors there become operating errors. Check each screen for five things: every value has a unit and a tag, the setpoint sits beside the actual value, alarm colours follow one convention, stale values look different from live ones, and room names match the room codes.
ICH Q2(R2) says validation demonstrates that an analytical procedure is fit for its intended purpose. A study typically shows specificity or selectivity, a range with suitable response and lower limits, accuracy and precision; robustness is typically evaluated in development under ICH Q14. Validated for one sample type does not mean validated for another.
The US chapter USP <800> holds a hazardous-drug compounding room at 0.01 to 0.03 inches of water column negative to adjacent areas, about 2.5 to 7.5 Pa. The band has an upper limit as well as a lower one, so the transmitter, the exhaust control and the tightness of the room all matter more than in a 10 to 15 Pa cascade.
Cleaning validation is often reduced to showing the previous product is gone. EU GMP Annex 15 (2015) also says limits should be established for cleaning agents, microbial and endotoxin risk should be considered when protocols are developed, and the times before and after cleaning should be used to define dirty and clean hold times.
A locked isolator does not stop a fan that windmills in the draught from a neighbouring unit. Isolating an AHU means identifying every energy source, moving air included, shutting down and isolating, one personal lock per worker, releasing stored energy, and trying to start the unit before the door is opened.
Below 0 °C, moisture in air can be stated as a dew point over supercooled water or a frost point over ice, and the frost point is the warmer number. At a frost point of −40 °C the dew point is about −43.7 °C. A dry-room specification should say which one it means.
Analytical methods are often the last work package in a product transfer. The WHO guideline (TRS 1044, Annex 4) says analytical procedures, including those for cleaning residue samples where applicable, should be implemented at the testing laboratory before process validation samples are tested. That takes qualified laboratory equipment and trained analysts ahead of the first batch.
Every SKU changeover on a packaging line is a chance for a leaflet or label from the previous run to reach the next. EU GMP Chapter 5 says line clearance should follow an appropriate checklist. Five checks cover it: nothing left behind, printed materials matched, counters at zero, bins empty, a second-person check.
A chilled water coil piped in parallel flow still cools, so the error often survives commissioning. It shows as a valve at 100%, return water colder than design and an off-coil temperature that misses setpoint. Mark inlet and outlet at the factory, check at FAT, and look again before the insulation goes on.
ICH Q10 defines the pharmaceutical quality system as the management system to direct and control a pharmaceutical company with regard to quality. It has four elements (monitoring, CAPA, change management, management review) and two enablers (knowledge management, quality risk management). SOPs are how the system is written down.