What a supply-duct RH sensor is good for

Air leaving a coil at 12 °C and 95% RH reads about 50% RH at 22 °C with the same 8.3 g/kg of water. A duct RH sensor after the coil works at the top of its scale. Control the coil on dew point or leaving-air temperature, and keep duct RH after reheat as a wet-filter alarm.

InsightRead

Pressure taps and tubing that tell the truth

A 3 m/s supply jet near a pressure tap can shift the reading by up to about 5 Pa, down or up depending on its angle, which is a third to half of a 10–15 Pa cascade. Tap position, tubing without low loops, matched tube lengths and a still reference port decide whether a room pressure trend is trustworthy.

InsightRead

EN 1886 casing: five classes on one datasheet

An AHU casing is described by five EN 1886 classes: strength D1–D3, leakage L1–L3, filter bypass up to F9, thermal transmittance T1–T5 and thermal bridging TB1–TB5. A witnessed FAT can test leakage on the real unit; transmittance and bridging come from a laboratory model box, so the model box report belongs with the offer.

InsightRead

A CCS nobody reviews is only a snapshot

Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated. A yearly meeting catches changes late. Adding one question to every HVAC change control, EM adverse trend review and deviation closure form, asking whether the CCS still says the right thing, keeps it current with the site.