Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Everything

From the Humiley newsroom

Announcements and company updates, alongside the technical notes our engineers publish from each practice.

What a harmonic study contains

A harmonic study has five parts: the single-line diagram and fault level at the point of common coupling, the harmonic spectra of the non-linear loads, a measurement of existing distortion, a network model compared with voltage and TDD limits, and a measurement after the mitigation is installed.

InsightRead

Annex 11 and the BMS-to-EMS link

The 2011 text of Annex 11 (clause 5) says systems that exchange data electronically should include built-in checks for correct and secure entry and processing. On a BMS-to-EMS link we read that as status flags, a communication watchdog, end-to-end checks of units and time stamps, and a loss-of-communication test in the qualification.

InsightRead

When 'read and understood' is the only training

A signature under 'read and understood' shows that reading happened. EU GMP Chapter 2 says training should be appropriate to the duties assigned and its practical effectiveness should be periodically assessed. Practical tasks need demonstration, supervised practice and an observed assessment, with SOPs sorted by risk to make that affordable.

InsightRead

A 75% RH fixed point from table salt

A saturated sodium chloride slurry in a sealed container holds the air above it at about 75% RH at 25 °C; magnesium chloride gives about 33%. The two points show whether a humidity probe has drifted between calibrations. It is a field check and does not replace a traceable calibration.

InsightRead

The drive-to-motor cable behind jittery pressure readings

Pressure readings that jitter when a fan changes speed often trace to the cable between drive and motor. Use screened symmetrical motor cable, bond the screen all round at both ends, keep it out of the signal tray, and stay within the drive's maximum cable length or fit an output filter.

InsightRead

Five things a quality agreement has to settle

The supply contract covers price and delivery. The quality agreement has to settle who is responsible for each GMP activity, how changes are notified and approved, how fast deviations and OOS results are reported, audit and subcontracting rights, and who keeps records and certifies the batch.

InsightRead

Knowledge management in ICH Q10, in plain terms

ICH Q10 names knowledge management as one of two enablers of the pharmaceutical quality system: a systematic approach to acquiring, analysing, storing and disseminating information about products, processes and components. In a technology transfer, that means handing over the reason behind each parameter, along with the batch record.

InsightRead

Cleaning validation does not follow the SKU count

Cleaning validation follows the residue and the equipment train. SKUs that differ only in pack share one bulk product, and EU GMP Annex 15 allows a justified worst-case product across a group. Changes between SKUs on the packaging line are controlled by line clearance under Chapter 5.

InsightRead

High room humidity: five checks, in order

Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.

InsightRead

How to read one row of the ASHRAE 170 table

Each hospital room type has one row in the ASHRAE 170 design parameters table, and every column is a design input: pressure relationship, outdoor and total air changes, whether air is exhausted outdoors, whether room units may recirculate, filtration, humidity and temperature. Read the notes, and check which edition applies.

InsightRead

A URS line such as 'alarm on low room pressure' cannot be tested as written. The functional specification says how the system will behave, function by function. In the usual V-model it faces OQ, so it should be numbered and approved before configuration starts, not reconstructed by the tester from the running system.

InsightRead